Pipe network heptafluoropropane(HFC-227ea) fire extinguishing system
Use "clean gas" heptafluoropropane as extinguishing agent
◆ Product features
  • Clean and liquid storage at normal temperature
  • Less than 10% of concentration and harmless to human body
  • Extinguishing without fouling and fast dissipation
  • Chemical way to extinguish fire, high efficiency
◆ Applicable object
  • Clean room
  • Computer control room
  • Precision instrument
  • Museums, Libraries
  • Communication equipment
  • Electrical machinery and power equipment
  • Chemical raw materials and oil products place
◆ System composition
  • The system is mainly composed of extinguishing agent bottle group, container valve, driving gas bottle group, electromagnetic drive device, selection valve, check valve, collecting pipe, safety valve, low leakage high sealing valve, signal feedback device, bottle rack, the nozzle, piping system and other equipment. According to the use requirements, various forms such as a unit independent system, a combination distribution system, and no pipe network cabinet type device may be formed, and fire protection for a single zone or multiple zones can be implemented.
◆ Working principle
  • Total flooding fire extinguishing system
    During a specified period of time, heptafluoropropane is injected into the protected area at a certain concentration, and it is evenly filled in the protected area. The heptafluoropropane fire extinguishing equipment is used to extinguish the fire by total flooding mode.
  • Unit independent system
    A set of fire extinguishing agent storage device corresponds to a set of network system to protect the composition of a protection zone. According to needs, it can be divided into a single bottle group independent system and a multiple bottle group independent system.

1.Safety discharge device 2.Drive gas circulation line check valve 3.Drive device (electromagnetic type)
4.Container valve (drive gas) 5.Drive gas bottle group 6.Extinguishing agent bottle group
7.Container valve (Fire extinguishing agent) 8.Pressure gauge 9.Low leakage high sealing valve
10.Pneumatic manual starter 11.Signal feedback device 12.Collecting pipe
13.Connecting pipe 14.Extinguisher circulation line check valve 15.Bottle holder
16.Nozzle 17.Emergency Start/Stop Button 18.Gas release door light
19.Sound and light alarm 20.Heat detector 21.Smoke detector
1.Safety discharge device 2.Drive gas circulation line check valve
3.Drive device (electromagnetic type) 4.Container valve (drive gas)
5.Drive gas bottle group 6.Extinguishing agent bottle group
7.Container valve (Fire extinguishing agent) 8.Pressure gauge
9.Low leakage high sealing valve 10.Pneumatic manual starter
11.Signal feedback device 12.Collecting pipe
13.Connecting pipe 14.Extinguisher circulation line check valve
15.Bottle holder 16.Nozzle
17.Emergency Start/Stop Button 18.Gas release door light
19.Sound and light alarm 20.Heat detector
21.Smoke detector  
  • Combined distribution system
    A set of shared heptafluoropropane storage devices correspond to several sets of network systems to protect the composition of two or more protection zones. Protection zones protected by a combined distribution system should not exceed eight.

1.Low leakage high sealing valve 2.Container valve (fire extinguishing agent) 3.Pressure gauge
4.Extinguishing agent bottle group 5.Driving gas bottle group 6.Container valve (drive gas)
7.Drive device (electromagnetic type) 8.Drive gas circulation line check valve 9.Select valve
10.Signal feedback device 11.Collecting pipe 12.Pneumatic manual starter
13.Connecting pipe 14.Extinguisher circulation line check valve 15.Bottle holder
16.Safety discharge Device 17.Nozzle 18.Emergency Start/Stop Button
19.Gas release door light 20.Sound and light alarm 21.Heat detector
22.Smoke detector  
1.Low leakage high sealing valve 2.Container valve (fire extinguishing agent)
3.Pressure gauge 4.Extinguishing agent bottle group
5.Driving gas bottle group 6.Container valve (drive gas)
7.Drive device (electromagnetic type) 8.Drive gas circulation line check valve
9.Select valve 10.Signal feedback device
11.Collecting pipe 12.Pneumatic manual starter
13.Connecting pipe 14.Extinguisher circulation line check valve
15.Bottle holder 16.Safety discharge Device
17.Nozzle 18.Emergency Start/Stop Button
19.Gas release door light 20.Sound and light alarm
21.Heat detector 22.Smoke detector
◆ Technical specification
Steel bottle specification 70L 90L 120L
Extinguishing agent amount (Kg) 2.45 3.15 4.20
Bottle group height (mm) 945 1155 1460
Bottle group diameter (mm) ¢362.2
Extinguishing agent bottle group storage pressure (MPa) 4.2
Extinguishing agent filling density (kg/m³) ≤950
System operating temperature range (℃) 0~50℃
System operating power AC220V/DC24 V
Maximum single area protection area (㎡) 800
Maximum single area protection volume (m³) 3600
System startup method Electric automatic, Electric manual, Manual air-operated start, Mechanical emergency operation
◆ Certificate

COPYRIGHT © 2018 Wuxi Brightsky Electronic Co.,Ltd. ALL RIGHT RESERVED.
ICP 11076333-1