IM501 Input module
Coded signal access equipment designed for various environments
◆ Product Features
  • The non-polar two-bus design can be regarded as the same fire detector connecting to the alarm buswhich is convenient for construction and flexible in use.
  • The numbering of the input device by the encoder makes it possible to display the specific address and working status on the alarm controller and the fire display panel.
  • Use isolated power (bus power) to power the feedback section
  • Using an ASIC, stable and reliable operation
◆ Technical specifications
Technical standard Meet the requirements of GB 16806-2006
Operating Voltage DC18~26V
Input signal Passive normally open contact (external termination resistance 4.7K)
Monitor current ≤300uA
Alarm current ≤1.5mA
Confirmation lamp (red) Run/input action lights (red):
Normally flash red,
Always on when there is input, no light when there is fault
Line system Two alarm buses: T+, T- (Non-polar)
Operating temperature -10℃~+55℃
Relative humidity ≤95%(40℃)
Dimensions 86mm×40mm×86mm(L×W×H)
Weight About 160g
Color White
◆ Wiring diagram

External terminal arrangement and description for IM501 Input module

Wiring instructions:
T+, T- : Alarm Bus (No polarity)
X1, X2 : Input passive signal (terminal resistance 4.7K)


◆ Certificate