Technical standard | Meet the requirements of GB 16806-2006 |
Bus Voltage | DC18~26V |
Power Voltage | DC24V |
Monitor current | Alarm bus T+, T-: ≤300uA External control power supply (DC24V) DC24V ≤2mA |
Alarm current | Alarm Bus T+, T-: ≤2.6mA |
Confirmation lamp (red) | Run/input action lights (red): Normally flash red, always on at startup, no light when there is fault |
Line system | Two alarm buses: T+, T- (non-polar), Two power buses: DC24V (non-polar) |
Contact capacity | DC30V 2A(AC120V 1A) |
Number of contacts | 2 pairs of normally open, normally closed contact synchronous conversion |
Operating temperature | -10℃~+55℃ |
Relative humidity | ≤95%(40℃) |
Dimensions | 86mm×40mm×86mm(L×W×H) |
Weight | About 160g |
Color | White |
External terminal arrangement and description for GM501 Output module
Wiring instructions:
T+, T-: Alarm Bus (No polarity)
P1, P2: 24VDC power supply (non-polarity)
XY1, XY2: Fire Radio
PY1, PY2: Normal broadcast
LB1, LB2: playback equipment (terminal resistance 100K)
COPYRIGHT © 2018 Wuxi Brightsky Electronic Co.,Ltd. ALL RIGHT RESERVED.