Smart City Smart Fire Safety
JK-GH2013G user information transmission device
A device that is set up at a networked client and transmits information to monitoring center through an alarm transmission network
The main equipment of urban fire control remote monitoring system
The first batch passed the city fire safety remote monitoring system GB26875.1-2011 standard certification
Relationship with Urban Fire Protection System Platform
Alarm Processing Flow
◆ Product Features
  • Adopt AC220V (main power) and DC12V (back-up power) to supply power, and both power supplies can automatically switch
  • With automatic detection function of local failure, automatic detection of main and backup power failures, automatic detection of communication failures with monitoring systems and monitoring centers
  • Receive fire alarms and operating status information of building fire-fighting facilities via the RS232/485 interface and upload them to the monitoring center
  • With manual fire button, manual fire alarm information can be uploaded to the monitoring center
  • GPRS/Ethernet can be used to upload alarm information to monitoring center
  • With the history record function, it can record the 5000 latest uploaded alarm information, power loss does not lose the data
  • With automatic registration function, registration time can be set remotely
  • On duty check function
  • Sound and light alarm indication
  • Chinese LCD display
  • Voice alarm
  • Voice intercom
◆ Technical Specifications
Main power AC 220V (+10%,-15%) 50HZ
Back-up power DC 12V,4AH (Internal)
Power consumption ≤10W
Back-up power continuous operation time ≥24 Hours
Communication method Alarm receiving RS232/RS485
Alarm upload GPRS / Ethernet
Communication distance RS232 ≤15m
RS485 ≤1000m
History record ≤ 5000 lists
Ambient temperature -10~50℃
Relative humidity ≤95%
Installation method Wall-mounted
Dimensions 280×100×390(L×W×H)
◆ Certificate

COPYRIGHT © 2018 Wuxi Brightsky Electronic Co.,Ltd. ALL RIGHT RESERVED.
ICP 11076333-1